Pressure equalization control PEC-1

Brand:

Two settings on the display are available with PEC-1 control.

  • The minimum fan speed can be set to match the idle capability of the fan controlled by the PEC-1 control.
  • The desired room static pressure is set to establish the control logic for pressure control.

Available options

  • PEC-1 controller only
  • Kit, PEC-1 controller and SPS-1 static pressure sensor

Pressure equalization control

Add To Quote
SKU: PEC

Do you have questions ?

Feel free to contact us !

Maintains static pressure at 0 or set value by changing fan speed

Digital static pressure display

Remote solid-state pressure transmitter

Adjustable minimum fan speed

Selectable control sensitivity

Can be use in exhaust or intake mode

No calibration required

INSTALLATION INSTRUCTIONS

  • The SPS-1 static pressure sensor can be installed up to 500 feet from the PEC-1 control unit.
  • A three-wire cable of 22 AWG conductors is used to connect the transmitter to the control unit.
  • The transmitter box can be located on either an inside wall or an outside wall, or even the ceiling if necessary.
  • If the transmitter is mounted outside, it must be in a protected location so that wind and weather does not disturb the air inlet to the transmitter.
  • If the transmitter is mounted on the inside of the building, the flexible vinyl tube that would be connected to the exterior probe inlet must also be in a protected location on the outside of the building.

Maintains static pressure at 0 or set value by changing fan speed

Digital static pressure display

Remote solid-state pressure transmitter

Adjustable minimum fan speed

Selectable control sensitivity

Can be use in exhaust or intake mode

No calibration required

INSTALLATION INSTRUCTIONS

  • The SPS-1 static pressure sensor can be installed up to 500 feet from the PEC-1 control unit.
  • A three-wire cable of 22 AWG conductors is used to connect the transmitter to the control unit.
  • The transmitter box can be located on either an inside wall or an outside wall, or even the ceiling if necessary.
  • If the transmitter is mounted outside, it must be in a protected location so that wind and weather does not disturb the air inlet to the transmitter.
  • If the transmitter is mounted on the inside of the building, the flexible vinyl tube that would be connected to the exterior probe inlet must also be in a protected location on the outside of the building.